Application of residual-based EWMA control charts for detecting faults in variable-air-volume air handling unit system (Q328257): Difference between revisions

From MaRDI portal
Importer (talk | contribs)
Created a new Item
 
ReferenceBot (talk | contribs)
Changed an Item
 
(5 intermediate revisions by 5 users not shown)
Property / review text
 
Summary: An online robust fault detection method is presented in this paper for VAV air handling unit and its implementation. Residual-based EWMA control chart is used to monitor the control processes of air handling unit and detect faults of air handling unit. In order to provide a level of robustness with respect to modeling errors, control limits are determined by incorporating time series model uncertainty in EWMA control chart. The fault detection method proposed is tested and validated using real time data collected from real VAV air-conditioning systems involving multiple artificial faults. The results of validation show residual-based EWMA control chart with designing control limits can improve the accuracy of fault detection through eliminating the negative effects of dynamic characteristics, serial correlation, normal transient changes of system, and time series modeling errors. The robust fault detection method proposed can provide an effective tool for detecting the faults of air handling units.
Property / review text: Summary: An online robust fault detection method is presented in this paper for VAV air handling unit and its implementation. Residual-based EWMA control chart is used to monitor the control processes of air handling unit and detect faults of air handling unit. In order to provide a level of robustness with respect to modeling errors, control limits are determined by incorporating time series model uncertainty in EWMA control chart. The fault detection method proposed is tested and validated using real time data collected from real VAV air-conditioning systems involving multiple artificial faults. The results of validation show residual-based EWMA control chart with designing control limits can improve the accuracy of fault detection through eliminating the negative effects of dynamic characteristics, serial correlation, normal transient changes of system, and time series modeling errors. The robust fault detection method proposed can provide an effective tool for detecting the faults of air handling units. / rank
 
Normal rank
Property / Mathematics Subject Classification ID
 
Property / Mathematics Subject Classification ID: 93B35 / rank
 
Normal rank
Property / Mathematics Subject Classification ID
 
Property / Mathematics Subject Classification ID: 93C95 / rank
 
Normal rank
Property / Mathematics Subject Classification ID
 
Property / Mathematics Subject Classification ID: 93B07 / rank
 
Normal rank
Property / zbMATH DE Number
 
Property / zbMATH DE Number: 6641341 / rank
 
Normal rank
Property / zbMATH Keywords
 
robust fault detection
Property / zbMATH Keywords: robust fault detection / rank
 
Normal rank
Property / zbMATH Keywords
 
residual-based EWMA control
Property / zbMATH Keywords: residual-based EWMA control / rank
 
Normal rank
Property / zbMATH Keywords
 
monitoring
Property / zbMATH Keywords: monitoring / rank
 
Normal rank
Property / Wikidata QID
 
Property / Wikidata QID: Q59125980 / rank
 
Normal rank
Property / MaRDI profile type
 
Property / MaRDI profile type: MaRDI publication profile / rank
 
Normal rank
Property / full work available at URL
 
Property / full work available at URL: https://doi.org/10.1155/2016/1467823 / rank
 
Normal rank
Property / OpenAlex ID
 
Property / OpenAlex ID: W2322186798 / rank
 
Normal rank
Property / cites work
 
Property / cites work: Spacecraft actuator diagnosis with principal component analysis: application to the rendez-vous phase of the Mars sample return mission / rank
 
Normal rank
Property / cites work
 
Property / cites work: Model-based fault detection and isolation of a liquid-cooled frequency converter on a wind turbine / rank
 
Normal rank
Property / cites work
 
Property / cites work: Q4862306 / rank
 
Normal rank
links / mardi / namelinks / mardi / name
 

Latest revision as of 18:10, 12 July 2024

scientific article
Language Label Description Also known as
English
Application of residual-based EWMA control charts for detecting faults in variable-air-volume air handling unit system
scientific article

    Statements

    Application of residual-based EWMA control charts for detecting faults in variable-air-volume air handling unit system (English)
    0 references
    0 references
    20 October 2016
    0 references
    Summary: An online robust fault detection method is presented in this paper for VAV air handling unit and its implementation. Residual-based EWMA control chart is used to monitor the control processes of air handling unit and detect faults of air handling unit. In order to provide a level of robustness with respect to modeling errors, control limits are determined by incorporating time series model uncertainty in EWMA control chart. The fault detection method proposed is tested and validated using real time data collected from real VAV air-conditioning systems involving multiple artificial faults. The results of validation show residual-based EWMA control chart with designing control limits can improve the accuracy of fault detection through eliminating the negative effects of dynamic characteristics, serial correlation, normal transient changes of system, and time series modeling errors. The robust fault detection method proposed can provide an effective tool for detecting the faults of air handling units.
    0 references
    robust fault detection
    0 references
    residual-based EWMA control
    0 references
    monitoring
    0 references

    Identifiers

    0 references
    0 references
    0 references
    0 references
    0 references
    0 references
    0 references